706.15 Precast Reinforced Concrete Outlets

1. Specification:

706.15 C&MS.

2. Sampling and/or Inspection Requirements:

Certified Plant Sampled and Tested Materials:

Sampling is not be required. Material is tested and accepted under certification program S 1073. The Certified Supplier list is on the OMM website at http://www.dot.state.oh.us/Divisions/ConstructionMgt/Materials/Pages/default.aspx. Materials from non-certified suppliers will not be accepted.

Inspect concrete outlets upon delivery to the project for dimensions and condition. Dimensions shall comply with the applicable Standard Construction Drawing or detail shown in the Plans. A TE-24 shipping notice must be received with the material. If the material fulfills the requirements it may be used immediately.

If the material does not fulfill the requirements, then it shall be rejected. Send a copy of the TE-24 to the DET and notify OMM, Concrete Section. (Field)

Sections shall be substantially free of fractures and surface roughness. Individual pieces may be rejected for the following:

Fractures or cracks passing through the wall

Defects that indicate imperfect proportioning, mixing and molding.

Surface defects indicating honeycomb or open texture.

Markings:

Each precast section shall be clearly marked with a production date

Manufacturer

3. Method of Tests:

(OMM Cement and Concrete Section)

S1073