725.05 Polyvinyl Chloride Conduit and Fittings

1. Specifications:

725.05 C&MS.

2. Sampling and/or Inspection Requirements:

Conduit, fittings and ells shall be inspected upon receipt of shipment for condition and conformance to the plans, specifications and/or approved catalog cuts. (Field)

Qualified Product List (QPL)

Only material that is approved as a Qualified Product may be used. To verify, refer to Qualified Product List (QPL) on the OMM website

http://www.dot.state.oh.us/Divisions/ConstructionMgt/Materials/Pages/QPL.aspx

. Suppliers who are interested in approval of their products should follow the requirements defined for this product on the list website.

No sample required.

3. Methods of Tests:

NEMA TC-2

4. Addendum:

Polyvinylchloride Conduit and Ells - Minimum Required Markings:

Nominal size

The letters "PVC"

The term "NEMA TC 2 or TC 6"

The letters "EB" or the letters "DB"

Manufacturers' name or trade mark

Items of Certified Data Required:

Duct Stiffness

Impact Resistance

Extrusion

Heat Distortion

Dimensions:

Diameters, Inches

Minimum Wall Thickness, (in.)

Nominal Duct Size

Minimum Inside

Outside Average

Outside Tolerance *

Type EB

Type DB

2

2.000

2.375

0.006

0.060

0.060

3

3.000

3.500

0.008

0.061

0.092

3-1/2

3.500

4.000

0.008

0.072

0.107

4

4.000

4.500

0.009

0.082

0.121

5

5.000

5.563

0.010

0.103

0.152

6

6.000

6.625

0.011

0.125

0.182