733 Traffic Signal Controller Material
733.01 References and Definitions.
“NEMA
TS-2,” “Type TS-2/A2,” and “Type TS-2/A1” refers to equipment manufactured in conformance with
the National Electrical Manufacturers
Association (NEMA) Standards Publication No. TS-2.
“NEMA
TS-1” and “Type TS-1” refers to equipment manufactured in conformance with
the National Electrical Manufacturers
Association (NEMA) Standards Publication No. TS-1.
“Type 332” and “Type 336” refers to equipment manufactured in conformance with
the California Department of Transportation (CalTrans)
specifications titled “Traffic Signal Control Equipment
Specifications” and “Transportation Electrical Equipment
Specifications“, including all addenda.
“Type 2070” refers to equipment manufactured in conformance with
the California Department of Transportation (CalTrans)
specifications titled “Transportation Electrical Equipment
Specifications”, including all addenda.
“CalTrans
QPL” refers
to the California Department of Transportation (CalTrans)
“Qualified Product List” for
traffic signal equipment.
“IP” refers to equipment conforming to the Internet
Protocol Suite communication protocols defined by the Internet
Engineering Taskforce RFC 1122.
A. General Requirements. Ensure that each controller unit contains
internal time based coordination and, if used in a hardwired coordination
system, provide an internal communication device or transceiver for connection
to interconnect cables including multi-conductor 120 volt cables, twisted pair
low voltage cables or fiber optic cables as shown on the plans.
If used in a closed
loop system, ensure that the local intersection controller contains all of the
software features necessary to operate with the system requirements given in 733.06
and 733.07.
Furnish the necessary communications capability for isolated local
intersections when part of the monitoring and control system described in 733.08.
When the signal
timing and phasing configuration shown on the plans requires a pre-timed
operation, ensure that the controller unit meets all requirements of this
section and can also be configured in a pre-timed, sequential phase, fixed
interval mode.
Furnish controller
memories that are nonvolatile and do not require batteries or other sources of
energy to retain data while power is removed from the controller.
B. Software. Furnish a communication port for connection to
a laptop computer for database upload/download. Furnish software for the
personal computer to completely program all features of the controller
unit. Unless otherwise shown on the plans, provide the controller unit
with software that provides the following features even if not used by the
signal phasing operation shown on the plans:
1.
NEMA 8 phase, dual ring capability with four
pedestrian movements, 4 overlaps, and the ability to program an exclusive
pedestrian movement. Ensure that the controller is capable of being
programmed for sequential phasing operation. All controllers shall be
capable of implementing Flashing Yellow Arrow operation by remapping pedestrian
channel yellow drivers to operate the yellow arrows.
2.
Volume density functions
3.
Secondary coordination plans
4.
Time of day/day of week scheduler
5.
Time based coordination, minimum 3 dials, 3 offsets, 3 splits
6.
Internal preemption for railroad and emergency vehicles. Railroad
preemption shall conform to ODOT specifications.
7.
Operator selectable single or dual entry in dual ring use
8.
Security access codes
9.
Detector features including delay timing, carryover (extension) timing and
detector switching
10.
Simultaneous gap out feature
11.
If operated in a system, communication capabilities to interface with hardwired
masters, dial up modems, and/or IP communication devices.
12.
Data upload and download capability to a personal computer. At least one
IP port and one serial port shall be included.
13.
Storage of detector counts utilizing phase detectors for a minimum 24 hour
period in 15 minute increments
14.
Detector failure monitoring and logging features for constant calls and absence
of calls
Furnish 60-month warranties
or for the manufacturers’ standard warranty, whichever is greater for the
following equipment:
1.
NEMA Controller Equipment
a. TS-2 Controller Units
b. Bus Interface Units
c. Malfunction Management
Units
d. TS 1 Conflict Monitors
2.
CalTrans Controller Equipment
a. Model 2010 Conflict Monitor Units
b. 2070L and 2070E
Controller Units including the following subassembly units:
(1) 2070-1E, 2070-1B CPU Board
(2) 2070-2A Field I/O Module
(3) 2070-3B Front Panel.
(4) 2070-6A,B.
Ensure that the
warranty period begins on the date of shipment to the project. Ensure
that each unit has a permanent label or stamp indicating the date of
shipment. Label shall indicate the equipment vendor name and or
logo.
C. Type TS
2/A1. Furnish a controller unit
that meets NEMA TS-2 specifications and is
shelf or rack mounted. Ensure that controller settings are programmable
through a keyboard on the front panel. Ensure that the front panel
contains an 8-line by 40-character display. Ensure the controller is equipped
with a datakey to support controller database
upload/download. Securely attach the datakey to the
top of the controller with fiber-reinforced tape at the time of delivery to the
project.
Furnish materials according to the Department’s Qualified Products List (QPL).
D. Type TS-2/A2. Furnish a controller unit that meets NEMA TS-2 specifications and is
suitable for shelf mounting. Furnish a controller unit that includes all
ports and input/output connectors for complete interchangeability between NEMA TS-1 and TS-2 cabinets.
Ensure that controller settings are
programmable through a keyboard on the front panel. Ensure that the front
panel contains an eight-line by 40-character display. Ensure the
controller is equipped with a datakey to support
controller database upload/download. Securely attach the datakey
to the top of the controller with fiber-reinforced tape at the time of delivery
to the project.
Furnish
materials according to the Department’s Qualified Products List (QPL).
E. Type 2070L. Furnish
controller units that meet the specifications for “Transportation Electrical Equipment
Specifications”, California Department of Transportation, including
all addenda. Furnish a controller unit that is listed on the ODOT Approved List.
The
Type 2070E version controller unit consists of the following assembled modules:
Unit Chassis
Model
2070-1B: CPU
module, single board
Model 2070-2A:
Field I/O module
Model 2070-3B:
Front panel, Display B
(8 lines of 40 char.)
Model 2070-4B:
Power supply module, 3.5 amp. [Power supply Model 2070-4A (10 amp) may be supplied in
lieu of Model 2070-4B]
Model 2070-7A:
Async.
Serial Communication Module
F.
Type 2070E. Furnish controller
units that meet the specifications for “Transportation Electrical Equipment
Specifications”, California Department of Transportation, including
all addenda. Furnish a controller unit that is listed on the ODOT Approved List.
The
Type 2070E version controller unit consists of the following assembled modules:
Unit Chassis
Model
2070-1E
CPU Module, Single Board
Model
2070-2A
Field I/O for 170 Cabinet
Model
2070-3B
Front Panel, Display B (8 lines of 40 characters)
Model 2070-4A or Model
2070-4B
Power Supply
Model
2070-7A
Async Serial Communication
Also,
equip all versions of the Type 2070 controller unit with the following:
1.
The appropriate communication port, cables, and connectors for communicating
with a laptop computer.
2.
Modems, ports, and cables for system communication, if the controller is to
operate as part of an interconnected signal system or has a telephone drop
shown on the plans.
3.
Furnish a serial communication cable to be used to establish periodic automatic
time sync between the 2070 controller software and the conflict monitor.
The cable shall consist of six feet (2 m) of unshielded 4- conductor cable, minimum 24 gauge stranded conductors with protective
jacket. End connectors shall be 9-pin D-subminiature with backshell, male and female, with pin assignments shown in
the table below.
9-pin Male |
9-pin Female |
3 |
3 |
5 |
5 |
2 |
2 |
1 |
4 |
8 |
4 |
4. 8Mb data key (SFK 8Mb).
Furnish materials
according to the Department’s Qualified Products List (QPL)
733.03 Cabinet. Ensure that all cabinets comply
with the requirements of this Section. Equip all NEMA
specified cabinets as follows:
Supply two
through four phase controller operation with a minimum twelve position backpanel, configured for four pedestrian movements and
four overlaps, with a twelve channel NEMA TS-1 conflict monitor or NEMA TS-2 malfunction management
unit.
Supply five
through eight phase controller operation with a minimum 12 position backpanel, configured for four pedestrian movements and no
overlaps, with a NEMA TS-2 malfunction management
unit.
For signal
phasing configurations that require a larger capacity backpanel
or conflict monitor, supply a 16 position backpanel
with a 16 channel NEMA TS-1 conflict monitor or NEMA TS-2 malfunction management
unit.
Furnish each cabinet main door with a sturdy, permanently lubricated lock that
is covered with a weatherproof tab. Key the project locks to the master
key used by the agency that will maintain the equipment. Supply two keys
with each lock. Also, equip the small door-in-door with a lock that is
keyed to the maintaining agency’s master key, covered with a weatherproof tab.
The door handle shall swing out away from the door edge, not toward the center
of the door.
Furnish cabinet with
drawings that show the following:
1.
Intersection map. The map shall include street names, all lanes,
crosswalks and stop bars, all vehicle and pedestrian phases, all loops and
detection zones, vehicular and pedestrian signal heads, and pedestrian
pushbuttons. All of these features shall be labeled. Include a
legend that shows the type of vehicular and pedestrian heads and north.
2.
Field wiring hook-up chart for all signal heads. The chart shall include
signal head name, signal head display indication, and field terminal on back
panel. See example below.
Signal Head |
G |
Y |
R |
G |
|
|
|
W |
DW |
1a |
2G |
2Y |
2R |
1G |
1Y |
|
|
|
|
2a |
2G |
2Y |
2R |
|
|
|
|
|
|
2b |
2G |
2Y |
2R |
|
|
|
|
|
|
4a |
4G |
4Y |
4R |
|
|
|
|
|
|
4b |
4G |
4Y |
4R |
|
|
|
|
|
|
4c |
4G |
4Y |
4R |
|
|
1G |
1Y |
|
|
6a |
6G |
6Y |
6R |
|
|
|
|
|
|
6b |
6G |
6Y |
6R |
|
|
|
|
|
|
8a |
8G |
8Y |
8R |
|
|
|
|
|
|
8b |
8G |
8Y |
8R |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
A |
|
|
|
|
|
|
|
9G |
9Y |
B |
|
|
|
|
|
|
|
10G |
10Y |
C |
|
|
|
|
|
|
|
11G |
11Y |
D |
|
|
|
|
|
|
|
12G |
12Y |
3.
Conflict Monitor/MMU channel assignments and
functions, switch positions, and settings. Also show program card jumper
locations diagrammatically (if applicable). If the Conflict Monitor/MMU is programmed via methods other than a program card
detail this diagrammatically.
4.
Legend with all wire gauges and insulator colors used in the cabinet.
Apply this legend to all wiring shown in the drawings. Also include
components such as MOVs and diodes.
5.
Detector panel wiring. Detail all detector landings.
6.
All cable and wiring harness pin assignments.
7.
Detector rack layout. Label detector number and associated phase.
8.
SDLC cable assignments.
9.
Pedestrian pushbutton wiring.
10.
Load switch assignments.
11.
Flash programming buss and field terminals wiring.
12.
I/O board, load switch, and flash transfer relay wiring.
13.
Any video, radar, preemption, or other device wiring, interface, and cabling
details.
14.
UPS as-built schematic (if applicable). Detail all connections to cabinet
and controller.
15.
Netlist detailing all connectivity of the cabinet.
It shall include all instances in the cabinet. Provide a description of
all instances.
1. Cabinets. Furnish a cabinet size that provides ample
space for housing the controller unit and all associated electrical devices
furnished with it, together with any other auxiliary devices that are
specified. Furnish a cabinet with sufficient shelf space to accommodate
all existing, proposed, and designated future equipment. Ensure
that the space provided accommodates the appropriate controller unit frame as
designated in NEMA TS-1, Section 14.
Construct the cabinets of cast aluminum or sheet aluminum, drawn or
formed, with aluminum support and stiffening of members provided as
necessary. Ensure that the exterior is smooth with no sharp edges.
Weld all joints. Ensure that the cabinet is rigid and is designed to
support all components. Ensure that the application of the following
loads do not result in breakage, deformation, or loss of weatherproof
qualities: a 100-pound (445 N) load applied to any 1-inch (25 mm) square
surface of the cabinet or door (open or closed), in any direction; or a
300-pound (1.3 kN) load applied vertically downward
to any 4-inch (100 mm) square of the top surface or to the top edge of the
closed and latched door.
Provide cabinet exterior surfaces of bare aluminum. When the
plans specify a cabinet color, prime and finish all cabinet exteriors with two coats
of high-grade enamel paint of the specified color. Ensure that the
cabinet interior surfaces are the same as the exterior, or may be painted flat
white.
Ensure that the
cabinet contains at least one rain-tight louvered vent equipped with a
replaceable filter. Install vents to allow for the release of excessive
heat and any explosive gases that might enter the cabinet.
Ensure that the
cabinets are functional in design and have a door in the front providing access
to substantially the full interior area. Attach a gasket of elastomeric
material to the cabinet or door to form a weatherproof seal. Furnish door
hinge pins of stainless steel or equivalent corrosion resistant material.
Furnish a door stop to retain the door in at least a 90 degree open position.
Include a small, hinged, and gasketed
door-in-door (police door) on the outside of the main controller door.
Ensure that the door-in-door does not allow entrance to the controller
mechanism nor to exposed electrical terminals, but provides access to a small
switch panel and compartment (police panel).
Fit the cabinet with the necessary provisions for mounting, with a
bottom conduit connection provided for pole-mounted cabinets. Furnish
suitable hardware and equipment for each cabinet mounting method, including
bolts for drilled and tapped holes on metal supports, pole attachment clamps,
pedestal slipfitter, and anchor bolts and conduit
ells for installation in concrete foundations. Furnish steel anchor bolts
that are galvanized at least 1 inch (25 mm) beyond the threads. Certified
cabinet anchor bolts are not required.
Directly place all
equipment designed for shelf mounting on a shelf except for loop detector units
(amplifiers) and similar devices designed for stacking on each other.
Arrange components on shelves and devices on the door so that a 1-inch (25 mm)
minimum space separates them when the door is shut. Ensure that plugs,
wires, controls, or similar items do not compromise this space.
Reserve a minimum
4-inch (100 mm) clear area on the bottom of the cabinet for the routing of
cables. Do not locate panel mounted equipment in the bottom 6 inches (150
mm) of the cabinet. Do not locate shelves or components within 6 inches
(150 mm) of the bottom of foundation mounted cabinets.
Arrange all equipment
for easy withdrawal and replacement, without the necessity of disturbing
adjacent equipment. Permanently locate devices within the cabinet to
allow free circulation of air and that do not restrict air flow from fan ducts
or vents.
Ensure that the
auxiliary equipment operates within a weatherproof cabinet at ambient
temperatures between ‑30 and 165 °F (-34 and 74 °C).
When terminals and panel mounted devices with exposed
electrical contact points are located next to shelf mounted equipment, provide
spacers, shelf lips, or other means to assure that component units cannot be
accidentally moved into contact with any exposed electrical terminal points.
Ensure that load
switches, relays, flashers, fuses, switches, terminal blocks, and other
equipment mounted or plugged into the back or side panels are readily
accessible. Ensure that switches, controls, and indicator lights are
visible and easily operable without moving the components from their normal
shelf positions.
Furnish materials
according to the Department’s Qualified Products List (QPL).
2. Accessory Equipment
a.
Ventilating Fan.
Equip all cabinets with a forced air ventilating fan. Furnish a fan
that provides a capacity of at least 100 cubic feet (2.8 m3) per
minute. Furnish a fan that is thermostatically controlled and adjusted to
start at cabinet temperatures above 120 °F (49 °C) and to stop when the
temperature has dropped below 100 °F (38 °C).
b.
Load Switches.
Furnish all cabinets with solid state, triple-signal load switches complying
with NEMA TS-1, Section 5.
Additionally, ensure that all load switches have both input and output
indicators.
c.
Conflict Monitor.
Furnish all cabinets with a separate solid-state conflict monitor device.
Ensure that the cabinet wiring, in the event of monitor disconnection,
transfers the signals to a flashing condition. Furnish conflict monitors
that comply with NEMA TS-1, Section 6.
Additionally, ensure that all conflict monitors are capable of causing the
signals to flash as a result of the following events:
(1)
All red lamps associated with a load switch are burned out;
(2)
Within one second when red and green, or yellow and green color pairings are
displayed on the same phase;
(3)
The absence of a minimum yellow interval.
Ensure that the monitor indicates the exact load switch output channel
upon which the failure event occurred. Furnish conflict monitors that are
capable of storing a minimum of nine fault
events (event logging feature). Furnish a monitor that utilizes a LCD
display and has a RS-232 port for connection to a laptop computer.
Furnish software and connector cables to diagnose the conflict monitor.
d.
Flashers.
Furnish solid-state flashers that comply with NEMA TS-1, Section 8.
When signals have a normal stop-and-go sequence that includes flashing, either
ensure that the controller unit generates that flashing display or provide
flashers. For this purpose, provide separate flashers from those provided
for emergency back-up. Furnish flashers that are designed with two
circuits of at least 10 amperes each.
Equip each controller cabinet with terminals that are wired so that, by
an interchange of jumpers, the flashing operation is arranged to display either
flashing yellow or flashing red on the vehicular signals.
e.
Relays.
Ensure that the relays required for proper operation of the specified equipment
are furnished and completely wired. Furnish relays that are enclosed,
readily replaceable, and designed for one-million operations without failure or
need for adjustment.
f.
Surge Protection Devices. Furnish surge protection on incoming power
lines, interconnect lines, and detector leads.
The
primary surge protection device (SPD) shall be an EDCO SHA-1250 or approved
equal. A plug-in base shall be used to hold the device. All wiring
connections shall be made to the base, and appropriate cabinet clearances
maintained, to allow the SPD module to be relaced by hand without the use of tools.
Furnish loop detector lead-in cable protection that consists of devices
installed in each detector circuit where the lead-in connects to the terminal
block. House each device in a case that consists of two stages; a
3-electrode gas tube arrestor and a semiconductor circuit. Ensure that
the arrestor shunts to ground a common mode transient with a 1,000 ampere peak
and an 8/20 microsecond wave-shape, ionizing at 400 volts within 100
nanoseconds when subjected to a 1,000 volt per microsecond transient.
Furnish a semiconductor circuit that clamps a differential transient to 30
volts within 40 nanoseconds of the appearance of the transient, and a common
mode transient to 30 volts within 500 nanoseconds of the ionization of the gas
tube arrestor. Ensure that the second stage is able to withstand a peak
current of 13 amperes. Furnish a device that has impedance
characteristics compatible with the detector unit so as not to cause false
calls or increase the loop impedance above the sensitivity of the detector
unit.
Furnish pedestrian pushbutton inputs with the same protection as
specified for the loop detector lead-in cables.
Protect interconnect cable against transients by devices across each
conductor of the cable and ground. The devices may be either 2 or
3-terminal devices. If 3-terminal devices are used, connect two
conductors and ground to the same device. Furnish a protection device
that consists of a gas tube arrestor with a maximum ionization voltage of 1000
volts on a 10,000 volt per microsecond transient or a maximum ionization
voltage of 950 volts on a 3000 volt per microsecond transient. Ensure
that the maximum time from beginning of the transient to ionization is 1.1
microseconds on a 10,000 volt per microsecond transient. Ensure that the
device is not ionized by normal voltage variations on a 120-volt AC line.
Furnish a device that is able to withstand a 10,000 ampere peak with an 8/20
microsecond waveshape.
g.
Main Power Breaker.
Furnish an incoming AC+ power line that is controlled by a main circuit breaker
rated at 240 volts and an auxiliary breaker, with capacity and wiring as
specified in NEMA TS-1, Section 10.3.2.2
and Figure 10-4.
If
a power service disconnect switch is located before the controller cabinet, the
neutral (AC-) and the grounding bar in the controller cabinet shall not be
connected together as shown in NEMA TS-1, Figure 10-4.
h.
Radio Interference Filter. Furnish an incoming AC+ power line that
contains a radio frequency interference (RFI) filter installed between the main circuit breaker and
the solid state equipment. Also, provide RFI
filtering for the load switches and flasher, unless the equipment furnished
provides signal and flasher circuits switching at the zero voltage point of the
power line sinusoid wave form.
i.
Convenience Outlet and Light. Wire a convenience outlet
into the cabinet for use by electrical maintenance equipment. Ensure that
the outlet contains at least one standard duplex three-wire NEMA
5-15 receptacle of the ground-fault circuit-interrupting (GFCI)
type. Wire a second GFCI convenience outlet,
not fed thru the UPS system (if used). Furnish and mount a white LED lamp in
the upper portion of the cabinet. Furnish a door switch to control the
convenience light.
j.
Manual Control and Pushbutton. When required by the plans,
provide intersection controller units with means for substituting manual
operation of interval timing for automatic interval timing. Ensure that
manual operation provides the same interval sequence as when the controller
unit is operating automatically.
Obtain manual interval timing by a momentary pushbutton contact switch
mounted on a 5-foot (1.5 m) minimum flexible weatherproof extension cord.
Store that switch and cord behind the small door-in-door.
k.
Switches.
Furnish completely wired switches that are required for proper operation of
specified equipment. Clearly and permanently label switches as to
function and setting position, and ensure that they are accessible without the
necessity of moving components.
(1)
Signal Shutdown Switch. Furnish
a cabinet with a signal shutdown switch for turning off the power to the
signals at the intersection. Ensure that this switch only affects the
power to the signals, and allows the controller to continue in operation.
Locate the switch in the panel behind the small door-in-door (police door).
(2)
Auto/Flash Switch. Furnish a
cabinet with a flash control switch for activating the flashing of vehicular
signals in a preselected emergency flash display. Ensure that the
operation of the flash control switch causes a flashing display even under conditions
of controller unit malfunction or of its removal from the cabinet. Ensure
that the operation of the switch overrides any operation commands from a local
or remote time switch. Locate the switch in the panel behind the small
door-in-door (police door).
Program the transfer to and from flashing operation, when called
remotely or by a local time switch, to occur only at points in the cycle
allowed by the OMUTCD.
(3)
Automatic/Manual Transfer Switch.
Furnish a cabinet with an automatic/manual transfer switch. In the
automatic position, ensure that the controller unit automatically sequences the
signal head displays. In the manual position, ensure that the signal
phase or interval sequencing occurs only upon manual activation of the manual
control pushbutton. Locate the switch in the door-in-door (police
door). Ensure that it is unnecessary, when switching from manual to
automatic operation, or vice versa, to do so at any certain time or to make any
time adjustments.
(4)
Run/Stop-Time Switch. Furnish a
cabinet with a run/stop-time switch that activates the controller stop-time
feature when in the “stop-time” position. Locate the run/stop-time switch
on a switch panel in the cabinet.
(5)
Controller Shutdown Switch.
Furnish a cabinet with a controller shutdown switch that cuts off power to the
controller unit, conflict monitor, and detector units. Ensure that power
is not cut off to those components required to maintain flashing
operation. Locate the controller shutdown switch on a switch panel in the
cabinet.
(6)
Coordinated/Free Switch.
Furnish controllers operated in a coordinated system with a coordinated/free
switch. Ensure that this switch allows the choice of operating the
controller under the supervision of a coordination device or operating the
controller independently of coordination control. Locate the
coordinated/free switch on a switch panel in the cabinet.
(7)
Detector Test Switches. Furnish
momentary contact switches that will enter a vehicular or pedestrian call for
any actuated phase. Furnish a switch for each actuated phase vehicular
and pedestrian detection input. Conveniently group and label the
switches.
l.
Terminal Blocks.
Furnish cabinets that include terminal blocks mounted on panels on the walls of
the cabinet. Ensure that the blocks are not obstructed by shelf-mounted
devices. Furnish sufficient terminal sets for each individual harness
wire as well as for contacts of signal load switches, flasher transfer relays,
flasher, and other components. Also, provide separate terminal sets for
field wiring connections, including power, signal, interconnection, and
detector lead-in cables. Group terminal sets to separate higher voltage
(120 VAC) from lower voltage, and arrange them into
logical groups. Protect terminal blocks from accidental contact during
the installation and removal of shelf-mounted equipment. Locate the
blocks no closer than 4 inches (100 mm) from the bottom of pole and pedestal
mounted cabinets, and no closer than 6 inches (150 mm) from the bottom of
foundation mounted cabinets.
Ensure that the terminal points are UL listed as suitable to carry the
rated loading. Ensure that the capacity and size of the terminals are as
specified in NEMA TS-1, Section 10.2.5.
Ensure that the terminal points for signal field wiring for each circuit
accommodates at least four 12 AWG conductors with
spade type terminals.
Furnish terminal points for incoming power wiring that accepts either
spade terminals or bare stranded wire and are suitable for either aluminum or
copper conductors.
Space terminal sets for easy wiring. Furnish at least six reserve
terminal sets for controllers. Harnesses may terminate on the back of
terminal blocks using through-panel terminals. Clearly mark terminal sets
for ready identification including through-panel terminals that are identified
on both sides. Ensure that the contact between adjacent terminal points
are made by bus bar, or by wire jumpers having spade type terminals securely
attached to each end.
m.
Terminal Buses.
Furnish a cabinet with supply terminal buses fed from the line side of the
incoming 120 VAC power line, after the phase wire has
passed through the main power switch. Ensure that the requirements for
use of radio interference filters are according to Item 8 of this Section, with
the buses supplying load switches and with flashers being filtered when
required. Ensure that a signal bus relay controls power to the bus
supplying power for the signal load switches. . The following overrides NEMA requirements for signal bus relays. A
solid-state relay shall be used for the signal bus relay. The signal bus
relay shall maintain output equal to or above the rating of the cabinet main
overcurrent protection device over the NEMA TS-2 Environmental
Operating Range of -50 to +185 degrees F (-45 to +85 degrees C).
Furnish a common
terminal bus for the connection of the neutral wire of the incoming 120 VAC power line. Ensure that the common bus has
sufficient terminal points to accommodate all potential cabinet wiring as well
as field wiring. Use a separate common terminal, insulated from the
panel, for the interconnect common.
Furnish bus terminal
points that comply with Item 12 of this Section for conductor accommodation,
attachment and identification.
n.
Grounding System/Bus Bars. Furnish a cabinet that includes a grounding
system as specified in NEMA TS-1, Section 10.3.2.1
with an adequate number (minimum of three) of ground terminal points.
o.
Wiring.
Neatly organize and route the harnesses and wiring bundles to individual
terminals. Ensure that the harness provides a wire for each pin or
contact of the device. Connect each wire to a marked terminal
position. Use labeled spade type terminals or plug connections on all
harness wiring. Group and lash or restrain wire bundles in such a manner
that they will not interfere with the access to components, terminal blocks or
buses, or the legibility of terminal identification. Ensure that the
harnesses are of sufficient length to reach any point within the cabinet.
Ensure that the cables and harness bundles are easily traced through the
cabinet to their terminations. Route all wiring terminated on printed circuit
boards (as commonly done for BIU backpanel
connectors) at right angles to the pin array; no wires shall pass over the
connector pins.
Wire the cabinet so that controller pin connections associated with a
given phase number matches the phase number assigned to the specified traffic
movement as shown on the plans.
Furnish all wiring with stranded conductors. Ensure that the
wiring is adequate for the voltage and load that represents the ultimate load
of the devices connected. Ensure that the ampacity
rating of the wires are as specified in NEMA TS-1, Section 10.3.3.1.
Ensure that the wiring is color coded as follows:
(1)
Solid white, AC common.
(2)
Solid green or green with yellow stripes, equipment ground.
(3)
Solid black, AC line side power (AC+).
p.
Loop Detector Units.
Furnish loop detector units that comply with the requirements of NEMA TS-1, Section 15, with
the following modifications:
(1)
Furnish loop detector units that are shelf mounted and powered from 120 volts.
(2)
Ensure that the unit uses solid-state isolated output devices.
(3)
Furnish conductors in the cable harness for loop input pins that are twisted
three to five times per foot (300 mm).
(4)
Furnish detector unit electrical connection plugs or wiring harness that are
designed such that any multi-channel shelf mounted detector unit is readily
replaced with single channel detector units. Furnish only units with the
connector type required for single channel shelf mounted detector units, or by
wiring the controller back panel to single channel wiring harnesses which are,
in turn, plug connected to an adapter harness that is mated to the multi-channel
connector of the detector unit.
(5)
When shown on the plans, supply delay and extension timing capability on the
detector unit; otherwise, the controller unit software requirements of 733.02
will provide these features.
(6)
Ensure that the harness provides a wire for each pin or contact of the device.
(7)
Furnish loop detector unit with an LED or LCD display indication of call
strength (∆L/L or equivalent). This display shall be a bar graph or
numerical display with at least eight (8) discrete levels indicated.
If vehicle detector
types other than “loop” detectors are required by the plans, provide these
detectors by separate bid item.
Furnish TS-1 cabinets
according to the Department’s Qualified Products List (QPL).
1.
Furnish TS-2 cabinets that utilize a high speed data channel to connect the
controller unit, malfunction management unit, rear
panel (terminals and facilities), detectors and bus interface units and also
comply with the general requirements of 733.03. Furnish a prewired
cabinet with malfunction management unit, loop detector units, and all
accessory equipment as specified in NEMA TS-2, except as follows:
a.
Section 5.3.4, use detector racks for both Type 1 (A1) and Type 2 (A2)
controller units.
b.
Section 5.4.2.1, if a power service disconnect switch is located before the
controller cabinet, the neutral (AC-) and the grounding bar in the controller
cabinet shall be connected together.
c.
Section 5.4.2.7, provide an LED type light.
d.
Section 5.4.2.7.2, provide the LED lamp.
e.
Section 5.4.2.7.3, provide the door actuated light switch.
f.
Section 6.5.2.2.1, provide 2-channel detector units,
without delay/extension features (Type A). Furnish momentary pushbuttons on the
cabinet door or a detector rack panel for actuation of Detector BIU #9, channels 1-16, and the four opto-isolated
pedestrian detector inputs on BIU #1 and BIU #2. Permanently label these pushbuttons as “VEH DET 1” through “VEH DET 16” and “PED DET 1” through “PED DET 8.”
g.
Section 7.2, construct cabinets of sheet aluminum.
h.
Section
7.3, unless otherwise specified in the plans, provide a Size 5 cabinet for four
phase or less pole mounted cabinets, Size 5 for four phase or less ground
mounted cabinets, and Size 6 for 5 phase or more ground mounted cabinets.
Supply larger cabinets if required to house the equipment to meet the plan
requirements; such as master controllers, preemption devices, 16 position backpanels or special detection units.
Furnish all wire passages through and over metal edges with edge protection
polymer trim.
i.
Section 7.5.7, ensure that the police panel contains
switches for AUTO/FLASH, SIGNALS ON/OFF and AUTO/MANUAL in the police
panel. Furnish a pushbutton with a 5-foot (1.5 m) cord, and panel connector,
not hard wired.
j.
Section 7.7.3, supply unpainted cabinets.
k.
The following overrides the NEMA
requirements for signal bus relays. A solid-state relay shall be used for the
signal bus relay. This relay shall maintain output equal to or exceeding the
requirements of the cabinet main overcurrent protective device over the NEMA TS-2 Environmental
Operating Range of -50 to +185 degrees Farenheit.
2.
Furnish loop detector and pedestrian inputs that have lightning/surge
protection as specified in 733.03.A.2.f.
3.
Include loop detector racks with the necessary number of two-channel loop
detector units with the cabinet. When shown on the plans, supply delay
and extension timing capability on the detector unit; otherwise, provide the
controller unit software with these features. If vehicle detector types
other than “loop” detectors are required by the plans, provide these detector
units by separate bid item. If the special bid detector units use
standard TS-2 detector racks, furnish the racks as part of the pre-wired
cabinet.
Furnish loop detector unit with an LED or LCD display indication of call
strength (∆L/L or equivalent). This display shall be a bar graph or
numerical display with at least eight (8) discrete levels indicated.
4.
Furnish switches to control the controller unit and cabinet functions as
specified in the plans.
5.
Furnish load switches that have both input and output indicators.
6. The primary surge protection device (SPD) shall be an EDCO SHA-1250 or approved
equal. A plug-in base shall be used to hold the device. All wiring
connections shall be made to the base, and appropriate cabinet clearances
maintained, to allow the SPD module to be replaced by
hand without the use of tools. Cabinet power distribution shall conform to
Figure 5-4, NEMA TS-2 2003 v02.06. In
addition, locates a non GFCI NEMA
5-15 utility outlet on the right side power panel. This outlet shall be powered
independently of the UPS by direct connection to incoming utility power through
a 15-amp circuit breaker labeled “UTILITY OUTLET.”
7. Include serial and/or Ethernet cables, 4-feet
minimum length, to interface with laptop computer. Include all interface
software.
8.
Include datakey module. Provide a datakey with each controller, taped securely to the top of
the controller chassis..
9. Include an SDLC expansion
board with three available ports, mounted on a cabinet side wall.
10. Include an SDLC in-line surge
suppressor, EDCO SRS-BIU-15 or
equivalent, located at the controller SDLC port.
11. Furnish an aluminum shelf with integral storage compartment in
the space immediately below the controller. Ensure the storage compartment has
telescoping drawer guides for full extension. Ensure the compartment top has a
non-slip plastic laminate attached.
.
Furnish TS-2 cabinet
according to the Department’s Qualified Products List (QPL).
1.
General. Furnish Model 332L
cabinets that meet the specifications “Traffic Signal Control Equipment
Specifications” and “Transportation Electrical Equipment
Specifications”, California Department of Transportation.
Ensure that the manufacturer of the cabinets is listed on the CalTrans and/or ODOT QPL at the
time of delivery to the project.
2. Cabinets.
a.
Ensure that the cabinets are constructed of aluminum and are supplied unpainted.
An anodic coating is not required. Supply galvanized anchor bolts with
nuts and washers with each cabinet. Furnish 3/4-inch (19 mm) diameter by
16 inches (0.4 m) minimum length anchor bolts with an “L” bend on the
unthreaded end.
b.
Fit the cabinets with a PDA-2 power distribution assembly.
c.
When shown on the plans, provide the cabinet with door hinges that are “right”
or “left” mounted when facing the front of the cabinet.
3. Terminals and Wiring.
a.
“Hardwire” output files. Do not use printed circuit wiring in the output
file except for the red monitor board.
b.
Ensure that the vehicle and pedestrian detector field wiring inputs connect to
side mounted terminal blocks. Install terminal blocks and associated
wiring to the input file. Label the field wiring terminals of the side
mounted terminal block by a permanent screening process to identify the input
panel (I or J), the input file slot number (1 through 14) and the channel
terminal (D, E, J, or K). An example is “I4-E”. Ensure that all
terminals on these detector blocks are accessible without removing equipment
from the EIA mounting rack.
c.
Install red monitor cabling in the cabinets. Install a program board to
enable/disable red monitoring. Ship the cabinets with the red monitor
jumpers set in the “enable” position.
d.
Do not connect the pedestrian yellow load switch outputs to the conflict
monitor card-edge connector.
e.
Supply each cabinet with a cable at least 5 feet (1.5 m) long to connect a
laptop computer with the controller. Ensure that the cable has a DB-9
connector on one end, and a connector on the other end to mate with the C2 on
the back of the controller. The cable will allow a laptop computer to
upload/download data to the controller.
f.
Supply each cabinet with a Category 5e cable with 8P8C (RJ45) plug on each end,
minimum 5 feet in length. The cable will allow a laptop computer to
upload/download data to the controller.
g.
On the output file, wire pin No. 11 of each switchpack
connector to AC- so that the output indicators on dual indicator switchpacks will display properly.
4. Accessories.
a.
Fully equip the cabinets with two channel loop detector sensors, flashers,
flash transfer relays, power supply, AC and DC isolators, conflict monitor, switchpacks (with both input and output indicators), and a
DC isolator in slot 14 for flash sense/stop time. Do not switch the input
file channels from the standard layout in order to minimize the number of
two-channel detector units utilized. If vehicle detector types other than
“loop” detectors are required by the plans, provide these detectors under a
separate bid item.
In addition to the requirements
of Caltrans TEES, furnish
detector unit with an LED or LCD display indication of call strength (∆L/L
or equivalent). This display shall be a bar graph or numerical display with at
least eight (8) discrete levels indicated.
Furnish loop detector sensors
according to the Department’s Qualified Products List (QPL).
b.
Furnish a rack mounted detector test panel with test switches for all allthe 16 Channel Call inputs of BIU
9, labeled 1-16, and the 8 Pedestrian Detector inputs of BIU
1 and 2, labeled P1-P8vehicle and pedestrian phases. Furnish switches
with three position “on/off/momentary on” switches.
c.
Furnish a police panel in each cabinet that includes a removable pushbutton
with 5 feet (1.5 m) cord and three switches labeled AUTO/FLASH, SIGNALS ON/OFF
and AUTO/MANUAL. Wire the pushbutton cord to the controller harness
wiring by a molex plug connection and not through an
AC isolator. When placed in the manual position, apply “manual control
enable” to the controller and apply “recall” to all phases. Ensure that
activation of the push button “advances” the controller, except prohibit the
manual advancement during the minimum green, yellow, and red timing intervals.
d.
Furnish an aluminum shelf with integral storage compartment in the rack below
the controller. Ensure that the storage compartment has telescoping
drawer guides for full extension. Ensure that the compartment top has a non-slip
plastic laminate attached. Top of shelf shall be at least 30 inches and
no more than 48 inches above the workpad
surface. For cabinets with risers, this may require relocating the drawer
to a position below Input File #2.
e.
Ensure that each cabinet has two white LED lights installed at the top of the
cabinet, one near each door. Wire the lights to the door switches such
that opening either door will turn on both lights.
5. Surge Protection.
a.
Furnish surge protection on pedestrian and detector inputs. Furnish three
terminal surrestors equivalent to EDCO
models SRA-6LCA, SRA-6LCB, or SRA-6LC.
b.
Protect the cabinet’s incoming power lines with an EDCO SHA1250 or approved
equal surge protector in lieu of the CalTrans specified surge
protection. A plug-in base shall be used to hold the device. All wiring
connections shall be made to the base, and appropriate cabinet clearances
maintained, to allow the SPD module to be relaced by hand without the use of tools.
6.
Conflict Monitor. Ensure that
the conflict monitor unit was tested and accepted according to Supplement 1076.
a.
Materials and Warranties. Furnish electrical parts,
switches, and other elements of the installation that are of ample capacity to
carry the required current without excessive heating or drop of potential.
Use standard
industrial quality components (integrated circuit chips, transistors, diodes,
resistors, capacitors, etc.) wherever possible. Clearly identify these
components with the original identification. Designate the other vital
information such as voltage polarity, emitter or collector terminals, pin
locations, etc., by an approved industrial procedure. Ensure that the
major items or assemblies of equipment bear a nameplate, indelible marking, or
brand that identifies it as to type, model, catalog number, and manufacturer.
Transfer that manufacturers’ guarantees or warranties to the
Department upon delivery and acceptance of the equipment. Ensure that all
conflict monitors are warranted for a period of 60 months or for the
manufacturer’s standard warranty period, whichever is greater, for parts and
labor from date of shipment to the project or the ODOT Signal Shop. Ensure
that each unit has a permanent label or stamp indicating the date of shipment
and name of vendor supplying the unit and/or logo..
b.
General Requirements.
(1)
Minimum Standards. This
specification establishes minimum standards for Conflict Monitoring Devices
designed for use in Model 332 and 336 Traffic Signal Controller Cabinets
supplied to the Department.
(2)
Indicator Lights. Furnish
indicator lights that are water-clear (not colored or diffused lenses), ultra-
bright light emitting diodes (LED), whose states are clearly readable in direct
sunlight. Ensure that each conflict monitor channel provides separate
red, yellow, and green LEDs.
(a)
Furnish a GREEN AC POWER indicator light.
(b)
Arrange indicator lights in a vertical pattern with FAULT status lights as the
upper indications and the output channel lights as the lower indications [See 733.03.C.6.c.(1)
and 733.03.C.6.c.(9)].
An acceptable alternative is to provide a single fault indication and a
supplemental display that clearly indicates the fault type.
(c)
Ensure that a failure causes its respective indicator light to display.
(3)
Monitor Power. Ensure that the
Monitor does not use the 24VDC power supply being sensed to run any of its
internal circuitry. Ensure that the watchdog, stop time, external reset,
and 24VDC monitor input circuits are optically isolated from the Monitor
internal power supply and are conditioned to provide proper sense circuit
operation throughout the operating range.
(4)
Power Fail. Consider a line
voltage less than 85 V ac ± 2 V ac as a power failure. Ensure that a
power failure does not result in resetting the Monitor. Ensure that once the
Monitor is triggered by detection of a fault that it remains in that state
until a Reset Command is issued. Reset is issued only by the Front Panel
Control Switch or by the External Test Reset input.
(5)
Power Up. Furnish a Monitor
that is compatible with the Model 170E controller as well as the Model 2070
controller unit that requires several seconds to power-up. When power is
established, > 103 ± 2 Vac, the 2010 will power up
in the FAULT RELAY RECOVERY mode:
When power is
established, initiate FAULT RELAY RECOVERY. For an interval of 6.0 ± 0.5
seconds, the following will take place:
(a)
The Output Relay contacts remain closed, and the Stop Time output remains
active.
(b)
All fault monitoring functions remain suspended.
(c)
The AC POWER indicator light flashes at a 2 hertz rate.
At the end of this
time interval, the Monitor begins counting Watchdog transitions from the
controller and prepares to resume normal fault monitoring.
Ensure that the
resumption of normal Fault monitoring occurs when either:
(a)
The Monitor has counted 5 transitions between the True and False state from the
controller Watchdog; or
(b)
10 ± 0.5 seconds has elapsed from the time of LINE RECOVERY.
If the controller
Watchdog output does not become active, ensure that the Monitor goes into a
Latched Fault condition.
(6)
Cabinet Signals Monitored.
Furnish a Monitor designed to monitor Green, Yellow, and Red AC circuits at the
field output terminals of traffic signal cabinets. Monitor shall be
capable of monitoring Flashing Yellow Arrow channels. In addition,
monitor the cabinet 24VDC supply, and the Model 170E/2070 controller Watchdog
Timer output. These signals are processed by the Monitor circuitry, and
if a failure is determined to have occurred, ensure that a relay output contact
closure (FAILED state) places the cabinet and intersection into flashing
operation.
(7) Failed State Output
Circuits.
(a)
Use an electro-mechanical relay to provide the FAILED STATE output
circuit. Ensure that the relay contacts are normally closed (FAILED
STATE). In a NON-FAILED state (relay coil energized), ensure that the
contacts are open. The function of this output circuit is to initiate
flash operation within the cabinet and transfer field circuits from the switch
pack outputs to the flash bus during a FAILED STATE.
(b)
Furnish relay contacts that are rated for a minimum of 3 amperes at 120 V ac
and 100,000 operations. Ensure that the contact opening/closing time is
30 ms or less. Furnish contacts that present a
minimum impedance of 50,000 ohms in the open state.
(c)
Ensure that the Stop Time output is active whenever the output relay contacts
are in the FAILED STATE (closed). Ensure that it is inactive whenever the
output relay contacts are in the NON-FAILED (open) STATE.
(8)
Monitor Unit Reset. Furnish a
front panel momentary SPST pushbutton switch labeled
“RESET” to reset the Monitor to a Non-FAILED state and restores normal
monitoring operation. Position the switch on the front panel so that the
switch can be operated while gripping the front panel handle.
Ensure that the
External Test Reset input line resets the Monitor circuitry to a Non-FAILED
state and restores normal monitoring operation. Optically isolate it from
the internal circuitry. Ensure that a reset issuance by either source
(Unit Reset) is triggered by only the leading edge of the input signal (this
will prevent a constant reset due to either a switch failure or a constant
external input). Ensure that a constant reset input is ignored within 5
seconds of issuance.
(9)
Input Impedance. Ensure that
the input impedance for all monitored AC inputs are
200 kilohms ± 100 kilohms.
(10)
Connectors. Furnish PCB 28/56P
Type Monitor and Conflict Program Card Connectors. Ensure that all edge
connectors use the “bifurcated bellow” type contact or equivalent.
(11) Door Ajar Circuit.
Connect pin 24 to pin 25 on the Monitor PCB at the edge connector and ensure
that it is capable of carrying one ampere according to CalTrans specifications.
(12) Handle. Ensure that the handle placement and design is
such that no interference between the handle and a closed cabinet door exists.
(13) Fuse
Holder. Furnish low profile fuse
holders on the front panel.
c.
Functional Requirements.
(1)
General. The Monitor monitors
the cabinet for conflicts and unsafe operation. If an unsafe condition
exists, the Monitor will enter into a FAILED state. This places the
cabinet into flash operation and applies STOP TIME to the controller
unit. Ensure that the Monitor is designed to monitor red circuits, yellow
timing, multiple outputs, and lack of outputs on a switch selectable, per
channel basis. Specific conditions for failure follow:
(a)
24VDC FAIL. The cabinet +24
volts DC does not meet the specified thresholds.
(b)
CONFLICT. When the green or
yellow input to one or more channels is ON and they are not programmed as
permissive on the Conflict Program Card.
(c)
WATCHDOG TIMER (WDT) ERROR. When the 170E/2070 controller
unit watchdog output has ceased.
(d)
CONFLICT PROGRAM CARD AJAR. Illuminates, if the Conflict Program Card is removed or if it is
not properly seated in the connector. When it is not inserted into
the monitor, ensure that the warning indicator light is displayed.
(e)
MONITOR FAILURE. A fault is
detected within the operation of the 2010 Monitor itself.
(f)
MULTIPLE OUTPUTS. Simultaneous indications of Green, Yellow, or Red field outputs on
a single channel.
(g)
RED FAIL. No active field
outputs on a single channel (green/yellow/red).
(h)
YELLOW ERROR. The absence of a
minimum yellow field output during a green to red sequence. Minimum
yellow shall be 2.7 seconds ± 100 ms.
(2)
Operating Range. Furnish a
Monitor Unit that is fully operational using an 85 to 135 V ac power
source. Ensure that the Monitor suspends Fault monitoring below 85 V ac ±
2 V ac, closes the output relay, and de-energizes the AC POWER indicator light.
(3)
Watchdog Timing. Furnish
WATCHDOG Timing Circuitry to monitor the controller unit WATCHDOG output.
Ensure that the WDT Circuitry senses state changes
and the time between the last change. Ensure
that an absence of change for 1.5±0.1 seconds places the Monitor in a FAILED
state.
(4)
Channels Monitored. Furnish a
Monitor that senses and responds to conflicts and 24 VDC
failures whenever the AC line voltage is within the 85 to 135 V ac operating
range of the Monitor, except during FAULT RELAY OPERATION.
(5)
Yellow Inhibit. Furnish means
to selectively inhibit the monitoring of a Yellow channel input.
(6)
Power Fail after Fault. In the
event that the Monitor senses a fault, followed by a loss of operating voltage,
ensure that the initial Failure Status is retained in memory and is redisplayed
after restoration of power.
(a)
Once the Monitor is LATCHED in a fault condition for any reason, including the
removal of the Conflict Program Card, ensure that it REMAINS LATCHED, even through a power fail/recovery, until a RESET is issued by
the front panel reset switch, or by the external test reset line.
(b)
Display the status of the Green, Yellow, and Red inputs of all channels, at the
time the fault was latched. Ensure that a power loss does not affect the
retention of this data. An acceptable alternative is to save status of
all channels in memory and only display the latched fault.
(7)
Insertion/Removal of Unit.
Ensure that it is possible to insert and remove the Monitor while the cabinet
is energized without placing the cabinet into Flash operation provided
that: The cabinet door remains open and the reset switch is held
depressed while the unit is being inserted or removed. Any momentary disruption
of field signal indications is less than 500 ms.
(8)
Microprocessor Use. If a
microprocessor is used in the Monitor design, ensure that its program is
written so that:
(a)
Integrity tests are performed periodically on each memory cell of each memory
device, relevant to each device type.
(b)
Hardware external to the microprocessor circuits is employed to constantly
sense proper microprocessor operation.
(c)
The Monitor reverts to a FAILED state if a fault is detected with the
microprocessor or during integrity tests.
(9)
Front Panel Indicators. Ensure
that the Monitor has red/yellow/green indicators for channel inputs and
indicators to provide status and failure detection information. Furnish a
GREEN AC POWER indicator. Ensure that all indicators are clearly readable
in direct sunlight. Arrange and label the indicators as shown below:
(a)
AC POWER. Illuminates
when the incoming AC Line Voltage exceeds 103 ± 2V ac, and FLASHES during FAULT
RELAY OPERATION.
(b)
VDC FAIL.
Illuminates when the Monitor has detected a 24VDC failure.
(c)
CONFLICT. Illuminates
when a conflicting signal condition is detected.
(d)
WDT ERROR.
Illuminates when a Watchdog error is detected.
Do not provide a switch or similar device to disable WDT
monitoring.
(e)
PC AJAR. Illuminates
when the Conflict Program Card is removed or is not properly seated in its
connector.
(f)
MON FAIL. Illuminates
to indicate an internal Monitor failure.
(g)
RED FAIL. Illuminates
when the Monitor detects that there is no active output on any of the field
outputs that comprise a monitored channel. Ensure that the failed
channels are displayed on the corresponding channel indicators. If for
any reason red fail is not enabled, ensure that the red fail indicator light
flashes at approximately 2hertz.
(h)
MULT IND.
Illuminates when the Monitor detects simultaneous outputs on
more than one of the field outputs that comprise a monitored channel
(green/yellow/red). Ensure that the failed channels are displayed
on the corresponding channel indicators.
(i)
YELLOW. Illuminates
when the Monitor detects the absence of a minimum period of active yellow field
output during a green to red sequence. Ensure that the failed
channel is displayed on the corresponding channel indicator.
(j)
1, 2, 3, 48. Furnish
channel indicators that illuminate a FAILED state in conformance with 733.03.C.6.c.(6).
(10) Monitor
Board Edge Connector. Furnish
monitor board edge connectors that conform to CalTrans specifications.
(11)
Monitoring of Conflicting Voltages.
Ensure that inputs to any channel that exceed the specified conflict threshold (see
Section 6) are sensed as “ON” and illuminate their respective channel
indicators. Ensure that the number of active channels in no way affects
the conflict threshold.
Ensure that the
following voltage levels and times apply: A conflict has occurred and
will cause a FAILED state only when voltages appear at the field output
terminals.
> 20 ± 5.0 V rms for a duration > 350 ± 150 ms.
(12)
Conflict Program Card. Furnish
conflict program cards that comply with CalTrans specifications.
d.
Fault Relay Operation.
(1)
Line Drop Out. Furnish a
Monitor that determines that a LINE DROP OUT has occurred when:
The AC Line Voltage is:
<
98 ± 2 VAC for > 400 ± 100 ms.
Within this time
frame, ensure that the Monitor suspends all fault monitoring functions, closes
the output relay contacts, enables Stop Time output, and the AC POWER indicator
on the front panel flashes at a rate of 2 hertz ±20 percent to indicate LINE
DROP OUT status. Ensure that the Monitor remains in the FAULT RELAY mode
until a LINE RECOVERY has occurred.
(2)
Line Recovery. Ensure that the
Monitor that determines that a LINE RECOVERY has occurred when:
The AC Line Voltage is:
> 103 ± 2 VAC for > 400 ± 100 ms.
(3)
Fault Relay Recovery. When LINE
RECOVERY is established, initiate the FAULT RELAY RECOVERY. For an
interval of 6.0 ± 0.5 seconds, the following will take place:
(a)
The Output Relay contacts remain closed, and the Stop Time output remains
active.
(b)
All fault monitoring functions remain suspended.
(c)
The AC POWER indicator light flashes at a rate of 2 hertz ± 20 percent.
At the end of this
time interval the Monitor begins counting Watchdog transitions from the
controller and prepares to resume normal fault monitoring.
(4)
Resumption of Normal Monitoring.
Ensure that the resumption of normal Fault Monitoring occurs when either:
(a)
the Monitor has counted five transitions between the
True and False state from the controller Watchdog; or
(b)
10 ± 0.5 seconds has elapsed from the time of LINE RECOVERY.
If the controller
Watchdog output does not become active, the Monitor shall go into a Latched
Fault condition.
e.
Red Monitoring Connector.
(1)
Connector. Mount a connector,
3M-3428-5302, with two 3518 polarizing keys, or equivalent, on the Monitor
front panel. The pin assignments of the P20 connector and terminal
assembly are defined in this specification.
Ensure that it is
possible to plug and unplug the Red Monitoring Connector P20 without placing
the cabinet into Flash operation.
P20 Connector Pin
Assignments
Pin |
Function |
Pin |
Function |
1 |
CHANNEL 15 RED |
2 |
CHANNEL 16 RED |
3 |
CHANNEL 14 RED |
4 |
UNDEFINED |
5 |
CHANNEL 13 RED |
6 |
SPECIAL FUNCTION 2 |
7 |
CHANNEL 12 RED |
8 |
SPECIAL FUNCTION 1 |
9 |
CHANNEL 10 RED |
10 |
CHANNEL 11 RED |
11 |
CHANNEL 9 RED |
12 |
CHANNEL 8 RED |
13 |
CHANNEL 7 RED |
14 |
CHANNEL 6 RED |
15 |
CHANNEL 5 RED |
16 |
CHANNEL 4 RED |
17 |
CHANNEL 3 RED |
18 |
CHANNEL 2 RED |
19 |
CHANNEL 1 RED |
20 |
RED ENABLE |
Ensure that keying is between pins 3/5, and 17/19. The odd
numbered pins are on one side, and the even pins are on the other. Key the
P20 connector and the CMU connector physically alike (to prevent the Red
Monitoring cable from being inserted into the P20 180 degrees out of
alignment).
(2) Red Enable Input. Ensure that pin 20 of the Red Monitoring
Connector provides the Red Enable input to the Monitor. When the Red
Monitoring Connector is disconnected, or Red Enable is not present, ensure that
the Monitor checks for conflicting combinations of Greens and Yellows, Watchdog
Timer, 24VDC, Conflict Program Card Ajar, and Monitor Fail. When enabled,
ensure that the extended Monitor functions become active including: Red
Fail, Multiple Output, and Yellow Fail.
(3) Special Function 1 and 2
Inputs.
(a) PIN 8, Special Function 1: Furnish an
AC input to the Monitor, which will DISABLE only the RED FAIL monitoring
functions while it is active (e.g. during Railroad Preempt).
(b)
PIN 6, Special Function 2: Reserved for future use.
Furnish a means to
select either a PRESENCE of, or LACK of AC+ to enable these inputs.
f.
Electrical Requirements.
(1)
Operation Range. Furnish
a Monitor that is fully operational from an 85 to 135 V ac power source.
(2)
Isolation. Isolate the Chassis
Ground and AC - from one another.
(3)
Monitored AC Inputs. The
following voltage and time thresholds apply to all monitored AC inputs.
(a)
Green and Yellow Inputs.
Any inputs < 15.0 V rms are considered OFF.
Any inputs > 25.0 V rms are considered ON.
Both sinusoidal and
half-wave inputs of the specified RMS values are to meet these thresholds.
(b)
Red, Red Enable, and Special Function Inputs.
Any inputs < 50.0 V rms are considered OFF.
Any inputs > 70.0 V rms are considered ON.
Red inputs, both
sinusoidal, and half-wave, of the specified RMS
values, are to meet these thresholds.
Red enable and
special function inputs are to meet these thresholds for sinusoidal waveforms
only.
(c)
Timing of Conflicting Inputs or Multiple Inputs.
Inputs ON < 200 ms are NOT considered a FAULT.
Inputs ON > 500 ms are considered a FAULT.
(d) Timing of Red Fail.
Lack of output < 1200 ms is NOT considered a FAULT.
Lack of output > 1500 ms is considered a FAULT.
(4) Monitored DC Inputs.
(a) 24VDC Input.
Input < 18.0 VDC is considered Low VDC input.
Input > 22.0 VDC is NOT considered Low VDC
input.
(b) 24VDC Timing.
Low VDC
input < 200 ms is NOT considered a FAULT.
Low VDC
input > 500 ms is considered a FAULT.
(c) Watchdog Monitor Input.
Input < 4.0 VDC is considered a LOW STATE.
Input > 12.0 VDC (or OPEN) is considered a HIGH STATE.
(d) Watchdog Error Timing.
Lack of valid input state
changes for < 1400 ms is NOT a FAULT.
Lack of valid input state
changes for > 1600 ms is a FAULT.
g.
Communications and Software.
(1)
Install an RS232 port for laptop communications on the front panel of the
Monitor. If specified in the plans, an IP port shall be used in place of
RS232.
(2)
Furnish a Monitor with compatible communications software for installation on a
laptop computer, capable of interfacing with the communication port on the
front panel. Furnish the software on a 3 1/2-inch (85 mm) floppy disk
with each Monitor. Label each disk with revision number and date.
(3)
Unless specified otherwise in the plans, furnish a Monitor that is capable of
being programmed and set-up for intersection operation without the use of a laptop computer and communication software.
(4)
Furnish a Monitor communications software that is capable of showing and/or
programming the status of all programmable set-up parameters of the unit.
Furnish a communications software that is capable of displaying the following
data:
(a)
Fault type
(b)
Field status (must update status continuously)
(c)
AC line voltage (must update status continuously)
(d)
Status of Red Enable
(e)
Previous fault data
(f)
Program card matrix
(g)
Yellow disable jumpers (if applicable)
(h)
Switch settings per channel (as applicable)
(i)
Option switches
(j)
Current time
(k)
Temperature (must update status continuously)
(l)
Event logs
(5)
Furnish a Monitor that is capable of storing events into memory. Typical
events are fault events, AC line events, reset events, etc. When a fault
event is stored into memory, the Monitor will store the fault condition (type),
channel status, date, time, temperature, and line voltage. Ensure that
the log history stores a minimum of 100 total events.
h.
Diode Matrix, Programming Key, and Software. Furnish a Monitor that
loads the diode matrix or Programming Key programming into a non-volatile
memory device. When the diode matrix or Programming Key is loaded into
memory, the memory will regularly compare with diode card or Programming Key
and fault condition will occur if memory does not match the diode card matrix.
Furnish
332 cabinet according to the Department’s Qualified Products List (QPL).
1.
General. Furnish Model 336
cabinets that meet the basic cabinet specifications “Traffic Signal Control
Equipment Specifications”, California Department of Transportation, latest
edition. Ensure that the manufacturer of these Model 336 cabinets is
listed on the ODOT or CalTrans QPL
for the Model 332 cabinets unless specified otherwise in the plans,
a 336L cabinet shall be furnished.
2. Cabinets.
a.
Furnish cabinets that are constructed of aluminum and are supplied
unpainted. An anodic coating is not required.
b.
The CalTrans Model 336 cabinet specification is only
modified so that the cabinet supplied is the “stretch” type that provides
approximately 10 inches of (250 mm) additional cabinet height.
c.
Supply galvanized anchor bolts with nuts and washers with each base mounted
cabinet. Furnish 3/4-inch (19 mm) diameter by 16 inches (0.4 m) minimum
length anchor bolts with an “L” bend on the unthreaded end.
d.
Furnish pole mounted cabinets with two pole mounting brackets attached and
bottom plates installed. Ensure that both of the cabinet sidewalls are
reinforced for pole brackets; however, also ensure that the cabinet is shipped
with the brackets installed on the door hinge side of the cabinet. When a
pole mounted cabinet is ordered, ensure that the door hinges are specified as
“right” or “left” mounted as looking into the front of the cabinet.
Ensure that the brackets are designed for banding to a pole.
e.
Fit cabinets with a PDA-2 power distribution assembly.
3.
Terminals and Wiring. Comply
with the requirements of 733.03.C.3.
4.
Accessories. Comply with the
requirements of 733.03.C.4.
5.
Lightning/Surge Protection.
Comply with the requirements of 733.03.C.5.
6.
Conflict Monitor. Comply with
the requirements of 733.03.C.6.
Furnish 336 cabinet materials according to the Department’s Qualified Products List (QPL).
733.04 Cabinet Risers. Furnish the type (size and
shape) of cabinet riser that is compatible with the type of controller cabinets
specified for the project.
A. Cabinet Riser
for NEMA Cabinet. Furnish an aluminum riser
that will raise the NEMA cabinet approximately 12
inches (0.3 m) above the concrete foundation. Ensure that the bottom of
the riser bolts to the standard cabinet foundation anchor bolts (not included
with the riser) and the top of the riser bolts to the bottom of the
cabinet. Furnish attachment hardware for connecting the riser to the
cabinet.
Construct
the riser in a minimum of two pieces such that an existing cabinet can be
raised off the foundation without disconnecting the field wiring and the riser
can be inserted below the cabinet. Furnish hardware for rigidly
connecting the riser sections together.
Fabricate
the riser from 0.125-inch (3 mm) sheet aluminum with flanges on the top and
bottom to provide rigidity. Furnish mounting flanges as necessary to
connect with the controller cabinet and foundation anchor bolts. Ensure
that the outside surface of the riser has a smooth, uniform, natural finish
unless controller cabinet painting is shown on the plans. If painting is
required, prepare and paint the riser to match the cabinet.
B. Cabinet Riser
for Type 332, 334 or Type 336 Cabinet. Furnish an aluminum riser that
will raise the Model 332, 334 or 336 cabinet
approximately 8 inches (0.2 m) above the concrete foundation. Ensure that
the bottom of the riser bolts to the standard cabinet foundation anchor bolts
(not included with the riser) and the top of the riser bolts to the bottom of
the cabinet. Furnish attachment hardware for connecting the riser to the
cabinet. Manufacture the unit to CalTrans specifications.
Ensure that the outside surface of the riser has a smooth, uniform, natural
finish unless controller cabinet painting is shown on the plans. If
painting is required, prepare and paint the riser to match the cabinet.
Furnish
materials according to the Department’s Qualified Products List (QPL).
733.05 Flasher Controller. Furnish
solid-state flasher that complies with NEMA TS-1, Section 8, and
have two circuits, each rated at 10 amperes. Furnish a cabinet that
conforms to applicable requirements of 733.03.A, except that the
following items are not required: a small door-in-door (police door),
shelves, and a fan. Ensure that the cabinet size is not less than
12 inches (300 mm) high by 10 inches (250 mm) wide by 6 inches (150 mm)
deep. Furnish cabinets that are designed for pole mounting with a 1-1/2
inch (38 mm) or larger conduit opening in the bottom. Ensure that the
auxiliary equipment includes: on-off power switch with integral 20-ampere
circuit breaker, lightning protection devices on incoming power lines,
interference filters, terminal blocks, and a ground bus bar.
Furnish
materials according to the Department’s Qualified Products List (QPL).
733.06 Controller, Master, Traffic Responsive.
A. Description. The traffic responsive master controller is one
component of a distributive processing, traffic responsive, control, and
monitoring “closed loop” system. The master controller’s principal
operational task is to select and implement traffic signal timing plans in
response to both actual traffic conditions or time based events. The
master controller monitors, in real time, local intersection activity, and
overall system performance, reporting failures and status conditions to the
Remote Monitoring Station.
The master controller
is typically located in a local intersection cabinet; however, in special
circumstances it may be located at a Remote Monitoring Station site. The
master controller is capable of uploading/downloading information to local
intersection controllers and the Remote Monitoring Station.
1.
Design. Furnish a solid state,
digital microprocessor master controller design. Furnish a controller
that uses menu driven prompts, unless of Type 170 design. If the master
controller is used with Type 170E or Type 2070 controllers, provide software
unless otherwise shown on the plans.
Furnish a master
controller that has a RS-232 port for connection to a laptop computer or
printer. Furnish software and connector cables for communication with a
laptop.
2.
Local Controllers. Ensure that
each master controller is able to supervise and communicate with at least 24
local intersection controllers.
3.
System Detectors. Ensure that
each master controller is able to analyze traffic sensor data from at least 32
system detectors. Distribute system detectors up to eight per
intersection, but do not exceed the total system sensor capacity.
Ensure that the
detectors are assignable to each of the computational channels in each group,
with the channels representing cycle selection, directionality (offset),
non-arterial flow (split), and special congestion indicators of queue or
occupancy.
Furnish a master
controller that is capable of monitoring and detecting system detector failure
and removing failed detectors from volume and occupancy calculations.
Upon resumption of satisfactory sensor operation, sensors shall automatically
resume input to volume and occupancy calculations.
4.
Timing Patterns. Ensure that
each master controller provides a minimum of 16 selectable patterns.
Ensure that each pattern shall consist of a combination of cycle, offset, and
split numbers for each intersection in the system.
Furnish a master
controller that is capable of implementing a “free” mode whereby all
intersection controllers will operate without system coordination and a “flash”
mode whereby all intersection controllers will operate in a flashing operation.
5.
Operational Modes. Ensure that
each master controller is able to operate in the following modes of operational
control:
a.
Traffic responsive mode whereby pattern selection is based on dynamic traffic
conditions as measured by system sensors located in the control area. As
a minimum, base the pattern selection on the quantitative traffic flow
parameters of volume, occupancy, and directionality of the arterial traffic.
Base transfer of patterns on programmable threshold
values. Furnish system
sensors that are capable of selective weighting.
b.
Time of day/day of week (time base) mode whereby pattern selection is based on
a preprogrammed event scheduler with automatic adjustments for seasonal
daylight savings time changes. Ensure that this mode of operation is able
to call or override traffic responsive mode.
c.
Manual override mode whereby pattern selection is made by operator control at
the Remote Monitoring Station or master controller site.
Ensure that the
system coordination control for each master controller is selected on a
priority basis. The priority from highest to lowest is as follows:
a.
Manual control entry or remote command
b.
Time base control
c.
Traffic responsive control
6.
Reports. Ensure that each
master controller monitors and formats intersection and system information for
immediate output to the Remote Monitoring Station or for storage for a minimum
period of 48 hours. As a minimum, ensure that the following types of
reports are generated:
a.
A local intersection activity log showing the time, date and activity of all
monitored local intersection failure conditions.
b.
A system sensor failure log that includes time, sensor location, and type of
failure.
c.
A system log with pattern changes.
d.
A system sensor data log that includes volume and occupancy for all system
sensors.
7.
Alarms. Ensure that each master
controller continuously monitors intersection and system information for
various systems and user defined critical conditions. Upon detection of
an alarm condition, ensure that the master controller attempts to transmit
alarm information to the Remote Monitoring Station or a preprogrammed telephone
number. In case of failure to connect to the central software, the master
will continue to periodically retry reporting to the Remote Monitoring Station.
8.
Communications. Furnish a
master controller that supports two-way dial-up communications to a Remote
Monitoring Station computer for control, monitoring, data collection, and for
timing pattern updating purposes. Through continuous, 7 days/week, 24
hours/day system monitoring, ensure that the master controller is able to
automatically dial-up the Remote Monitoring Station computer upon detection of
user defined critical alarm conditions.
Furnish a master
controller that includes any communication devices or modems necessary to
interface with the local intersection controllers within its control area.
9.
Security. Furnish a master
controller that provides for a user specified security code before any data is
altered. In order to view any parameter, ensure that a security code
entry is not required. Furnish a master controller that has the ability
to disable security code requirements, allowing for perpetual access without
requiring hardware changes.
733.07 Remote
Monitoring Station.
A. Description. The Remote Monitoring Station describes a
distributive processing, traffic responsive, control and monitoring “closed
loop” system. The system monitors, in real time, local intersection
activities, and overall system performance, reporting failures and status
conditions both automatically and by operator request. In order to meet
current and future traffic control needs, the system also provides extensive
control monitoring, data collection, reporting, and analysis functions.
For complete user
flexibility, the system provides full access of each local system intersection
controller from the Remote Monitoring Station site. Full access includes
the capability to upload all time settings, operation parameters, and status
information, as well as the capability to download all time settings and
operation parameters.
B. System Architecture. The system consists of four principal elements:
1. Local intersection controller (see 733.02)
2. Communication links
3. Traffic responsive master controller
(see 733.06)
4.
A Remote Monitoring Station consisting of computer equipment and software
C. Local Intersection Controllers. Furnish controller units conforming to 733.02
for the type of controller shown on the plans. Furnish a controller that
has internal communication capability compatible with the type of interconnect
cable shown on the plans. Furnish a local system controller that is
capable of processing controller and detector data and provide all necessary
intersection control functions.
D. Communications. Ensure that communication between the Remote
Monitoring Station and the master controller is through an
auto-answer/auto-dial external modem on standard dial-up telephone
service. Furnish telephone service at the Remote Monitoring Station site
by the maintaining agency, unless otherwise shown on the plans. Furnish
telephone service at the master controller or the isolated local intersection
location by separate bid item as specified for “Telephone Service”.
Include error
checking in the software to assure transmission and reception of valid data between
the local controller, master controller, and the Remote Monitoring Station.
E. Equipment. Ensure that the Equipment provided at each
Remote Monitoring Station location is as shown on the plans and, as a minimum,
consists of the following items:
1.
Microcomputer with monitor
2.
Software
3.
Modem
4.
Printer
5.
Accessory Items
F. System Functional Requirements. The system software provides a simplified user
friendly, color menu format at the Remote Monitoring Station. Ensure that
no special computer programming skills are required for the user to fully
access and operate this control and monitoring system.
1.
Graphical Representation.
Furnish system software that enables the operator to display in color, the vehicular
signals, pedestrian signals, and detector actuations in a real time mode.
Ensure that the user is able to construct an intersection layout graphically by
using predetermined intersection shapes.
2.
System Capacity. Furnish a Remote Monitoring Station software that has the capacity
to monitor and control at least 24 traffic responsive masters. Ensure
that the central software is also capable of monitoring and controlling
isolated system controllers.
Furnish a system software that has the capability to manually select
any timing plan, free mode or flash mode.
Ensure that the
system software has the capability of accepting, formatting, and processing
data from at least 32 system detectors from each master controller.
3.
Data Transfer. Ensure that it
is possible to upload/download the signal timing database, including
coordination, and preemption settings, between the Remote Monitoring Station
and the master controller or local intersection.
Furnish a Remote Monitoring Station that provides a means to compare a
currently uploaded timing database with a previously developed database stored
in the Remote Monitoring Station memory. Ensure that it reports
differences in the databases.
During either uploading or downloading operations, ensure that the
normal traffic control operations are not suspended.
4. Security. Furnish a Remote Monitoring Station that
provides for a user specified security code before any data is altered.
Maintain controller access procedures from the Remote Monitoring Station
allowing the user full security control of all system components from a remote
location.
5. Isolated Intersection
Management. Furnish a Remote Monitoring Station software that includes the
capability of accessing system controllers at remote intersection
locations. Ensure that this capability includes total access to
controller timing parameters, alarm conditions, detector data, and intersection
status conditions in real time without the use of a master controller.
Ensure that this feature utilizes the local intersection controller with a
dial-up modem and telephone service.
733.08 Telephone Service. Ensure
that the telephone service is a standard dial-up service capable of supporting
2400 baud data transmission. Ensure that the external modem provided is a
Hayes compatible, auto-answer/auto-dial unit with all connections, cables, and
lightning protection on the incoming wires provided.
733.09 Uninterruptible Power Supply(UPS).
A. Operation. In addition
to the material requirements below, furnish a UPS system with a minimum two and
one half (2.5) hours of full run-time operation for an “LED-only” intersection
with 1000 watts of active output power.
Furnish a UPS compatible with all of the following traffic signal equipment; NEMA TS-1 and TS-2 controllers and
cabinets, Model 332 & 336 cabinets, Type 170 & 2070 controllers and
electrical service pedestals.
The maximum transfer time allowed, from disruption of normal utility line
voltage to stabilized inverter line voltage from batteries, shall be 65
milliseconds or less. The same maximum allowable transfer time shall also
apply when switching from inverter line voltage to utility line voltage.
Include a means to switch the intersection from full-operation to flashing
operation after 2-hours of run-time. This is to conserve battery operation
during an extended utility power outage.
Include standard form C relay contacts to trigger an alarm within the
controller assembly, informing a technician the system is operating on battery
backup.
Operating temperature for both the inverter/charger, power transfer relay and
manual bypass switch shall be -35 °F to +165
°F (-37 °C to +74 °C).
Both the power transfer relay and manual bypass switch shall be rated at
240VAC/30 amps, minimum.
The UPS shall bypass the utility line power whenever the utility line voltage
is outside the following voltage range: 100VAC to 130 VAC,
+ 2 VAC.
When utilizing battery power, the UPS output voltage shall be between 110 VAC and 125 VAC, pure sine wave
output, 60Hz ± 3Hz.
When the utility line power has been restored between 100 VAC
and 130 VAC for more than 30 seconds, the UPS shall
dropout of battery backup mode and return to utility line mode.
In the event of inverter/charger failure, battery failure or complete battery
discharge, the power transfer relay shall revert to the NC (and energized)
state, where utility line power is connected to the cabinet.
Recharge time for the battery, from “protective low-cutoff” to 80% or more of
full battery charge capacity, shall not exceed 10 hours.
Include all necessary wiring and hardware for mounting (shelf angles, rack, etc).
Furnish a UPS with available buck/boost
mode operation, with a minimum input voltage
range of 85 to 150 vrms. The unit display shall
indicate when buck/boost mode is engaged. Default
buck/boost setpoints shall be 108 vrms
and 132 vrms unless specified otherwise in the Plans.
Furnish a UPS with an
Ethernet port for remote monitoring and control. Provide interface software
unless the Ethernet port has built-in web browser compatibility. Remote
communication shall have the ability to make setting changes, review status,
retrieve alarm and event logging that is time and date stamped for up to 50
events. The logs shall be printable.
Ensure the UPS
cabinet has a mastic tape seal between the cabinet bottom flange and the
concrete foundation. Minimum tape thickness shall be 1/8-inch (3 mm) and the
tape shall be continuous with no gaps between tape pieces or between cabinet
and foundation.
The UPS output
notifications for on battery, battery 2 hour timer and low battery shall be
wired into the traffic signal back panel to provide special status alarms for
each output into the signal controller.
This item shall
include a red LED status indicator lamp to allow maintenance personnel and law
enforcement to quickly assess whether a traffic signal cabinet is being powered
by a UPS. The LED housing shall be NEMA 4X,
IP65 or IR66, rated for outdoor use and be tamper/shatter resistant. It
shall be a domed enclosure contained a red lens with LED that is visible from
100 foot minimum. The enclosure and LED lamp unit should be placed and
centered on the top surface of the UPS cabinet and sealed from water
intrusion. It should be wired using minimum 20 GA stranded, insulated
hookup wire to the status relay outputs of the UPS.
The wires shall be
terminated by lugs at the display end and permanently labeled "Backup
Power Status Display," with wire polarity indicated. The red LED
shall only illuminate to indicate the cabinet is operating under UPS backup
power (the "backup" operating condition). This item also
includes programming the UPS status relay outputs to produce the lamp status
displays. These status displays will be solid 100% duty cycle (not flashing)
displays. The operating voltage of the LED lamp shall be 120V AC unless
otherwise indicated.
B. Maintenance, Displays,
Controls and Diagnostics. Furnish a UPS with a backlit LCD display that
includes an event counter, hour meter, line and battery voltages/percentages
and fault status. The LCD display shall have touch keys for changing
display statuses and to reset counters, hour meter date and time.
Furnish a UPS with lightning surge protection compliant with IEEE/ANSI C.62.41.
Furnish two (2) sets of equipment lists, operation and maintenance manuals, and
board-level schematic and wiring diagrams of the UPS, and the battery data
sheets. Manual shall conform to TEES 1999, Chapter 1 Section
1.2.4.2.
C. Battery System. Supply a
minimum of four (4) batteries with the UPS system. Each battery shall be 12VDC
and be rated at a minimum of 95 Ahrs, 20-hour
discharge rate to 1.8 volts/cell at 77 degrees Fahrenheit (25 degrees Celsius),
to achieve the 2.5 hour run time requirement. Furnish batteries easily replaced
and commercially available off the shelf.
Furnish deep cycle, sealed prismatic lead-calcium based AGM/VRLA (Absorbed Glass Mat/ Valve Regulated Lead Acid)
batteries.
Furnish batteries certified in writing by the manufacturer to operate over a
temperature range of -13 °F to +165 °F (– 25 °C to +74 °C).
Place all batteries on battery heater mats in the enclosure. The battery heater
mats are designed to extend the life of the batteries.
An integral system shall prevent the battery from destructive discharge and
overcharge. Batteries shall not be recharged when battery temperature exceeds
122°F±5°F(50°C±3°C).
D. Enclosure. Furnish
an enclosure mountable to a standard Model 332, NEMA TS-1 or TS-2 traffic signal
cabinet and be constructed of natural unpainted aluminum. Furnish cabinet
size adequate to house “all” the UPS equipment including the controller unit,
manual bypass switch and the (4) batteries. Key the enclosure
to the State master #2 lock and include 2 keys.
Furnish
a base seal for use between the enclosure to the concrete foundation or riser
of continuous tape gasket material, minimum 1/8-inch (3 mm) thickness.
Completely seal the interface to the adjacent controller cabinet with silicone
caulk.
Furnish
an enclosure with a vent, fan and thermostat as per TEES Chapter 7, Section
2-Housings.
E.
Warranty. Provide a two (2) year factory-repair warranty for parts and
labor on the UPS from date of acceptance by the State. Warrant batteries for
full replacement for two (2) years from date of purchase.
Furnish materials according to
the Department's Qualified Products List (QPL).